Mesa outdoor lighting code — what a site-lighting design must meet

Outdoor lighting code · transcribed from adopted text · verified August 8, 2026

Mesa's ordinance is written around the meter reading at the property line and the wattage of the lamp on the pole. Every number below comes from Mesa City Code §4-4-1; Zoning §11-30-5 (through Ord. 5996), the same rule file our Lighting Design Tool computes with — nothing retyped. Ordinances change: confirm current requirements with the authority having jurisdiction before submittal.

Mesa regulates outdoor lighting with a spillage limit in foot-candles at the property line, shielding by lamp class and pole heights tied to lamp wattage. The at-a-glance table is the code’s own table, reproduced; everything after it is the rule text that changes a design.

At a glance: every transcribed requirement

Outdoor lighting requirements, transcribed
RuleStatusWhat the code says
mesa-spillRequiredLight spillage at any property line, measured 36 in. above grade: max 0.5 fc above ambient — 0.3 fc where the line abuts residential use. Adjacent to a public street, the line may be taken at the street centerline (§4-4-1(G)).
mesa-shieldRequiredShielding by lamp class (Table 4-4-1(F)): metal halide fully shielded + filtered; fluorescent partially shielded + filtered; HPS/quartz partially shielded; incandescent over 150 W partially shielded (≤150 W exempt). Internally illuminated translucent signs exempt. No lamp over 150 W (incandescent-equivalent) may be directly visible from the property line.
mesa-heightRequiredPole heights: 15 ft within 50 ft of residential, 20 ft within 50 ft of other perimeter uses, 25 ft elsewhere, with house-side shields adjacent to residential (§11-30-5). Wattage-based caps (Table 4-4-1(H)): 150 W→15 ft · 250 W→20 ft · 400 W→25 ft · 1,000 W→40 ft (HID; other lamps by equivalent lumens).
mesa-curfewRequiredAdvertising searchlights banned 11:00 PM–sunrise; mercury vapor prohibited; nonconforming fixtures and billboard uplighting need automatic shutoff by 11:00 PM; recreational facilities dark by 11:00 PM except to finish an event (§4-4-1(H),(I),(M),(N)).
mesa-flagNoteFlagpoles: up to 3 upward fixtures at ≤75 W each, still subject to the spillage limits (§4-4-1(P)).

How much the code actually pins down

4Hard requirements transcribed
1Recommendations and review notes
NoneLumen-per-acre budget

The trap that catches out-of-town designers

Mesa's number is at the property line, not per acre: light spillage may not exceed 0.5 fc above ambient at any line, or 0.3 fc where the line abuts a residential use, measured 36 in. above grade — and where the site fronts a public street the line may be taken at the street centerline (§4-4-1(G)), which is the relief most out-of-town photometric plans miss. No lamp over 150 W (incandescent-equivalent) may be directly visible from the property line. Pole heights are set two ways at once: by proximity (15 ft within 50 ft of residential, 20 ft within 50 ft of other perimeter uses, 25 ft elsewhere, house-side shields adjacent to residential) and by lamp wattage under Table 4-4-1(H) — 150 W to 15 ft, 250 W to 20 ft, 400 W to 25 ft, 1,000 W to 40 ft, with other lamps rated by equivalent lumens. Mercury vapor is prohibited, and nonconforming fixtures and billboard uplighting need automatic shutoff by 11:00 PM.

Underneath every city code: the state statute

  • Arizona statute: every outdoor light fixture must be fully or partially shielded unless it is an incandescent lamp of 150 W or less, or any other lamp of 70 W or less (ARS §49-1102).
  • Mercury-vapor fixtures may not be sold or installed anywhere in Arizona (ARS §49-1104).

The statute is the floor; the city or town ordinance above is what the permit is reviewed against. Where the two differ, the stricter applies.

Source, date and limits

Source: Mesa City Code §4-4-1; Zoning §11-30-5 (through Ord. 5996). Transcribed and verified: August 8, 2026, from the code text itself, never a summary site. Page updated: 5 September 2026. Status: current as of the verification date.

These pages render the same data file that drives our Lighting Design Tool, so a value here is the value the tool checks a design against. They are a reference, not a code book and not legal advice: the adopted ordinance, its amendments and the reviewer’s interpretation govern. Confirm with the authority having jurisdiction before you submit. IES illuminance targets and IECC power allowances are licensed-standard material and are not reproduced here.

Questions people ask

Does Mesa have a lumens-per-acre budget?

No. Mesa does not set a lumens-per-acre budget the way the dark-sky codes of southern and northern Arizona do; it regulates outdoor lighting through a spillage limit in foot-candles at the property line, shielding by lamp class and pole heights tied to lamp wattage. The first requirement in Mesa City Code §4-4-1; Zoning §11-30-5 (through Ord. 5996): Light spillage at any property line, measured 36 in. above grade: max 0.5 fc above ambient — 0.3 fc where the line abuts residential use. Adjacent to a public street, the line may be taken at the street centerline (§4-4-1(G)).

What is the light-spillage limit at the property line in Mesa?

Light spillage at any property line, measured 36 in. above grade: max 0.5 fc above ambient — 0.3 fc where the line abuts residential use. Adjacent to a public street, the line may be taken at the street centerline (§4-4-1(G)).

How tall can light poles be in Mesa?

Pole heights: 15 ft within 50 ft of residential, 20 ft within 50 ft of other perimeter uses, 25 ft elsewhere, with house-side shields adjacent to residential (§11-30-5). Wattage-based caps (Table 4-4-1(H)): 150 W→15 ft · 250 W→20 ft · 400 W→25 ft · 1,000 W→40 ft (HID; other lamps by equivalent lumens).

What must be off by 11 PM in Mesa?