Electrical permit history — 1901 N Wilmot Rd

1901 N Wilmot Rd, Tucson — built 1981, with 35 permits on record. Review electrical, HVAC and remodel history with links to official records.

Multifamily property

1901 N Wilmot Rd

Built 1981 — 1980s multifamily stock · last permitted panel/service work 2024 (permitted, completion not confirmed) · 6 open code cases

Parcel
12101012F
Built
1981 (county record)
Jurisdiction
Tucson
Zoning
R-3
Assessor use
Apartments 100+ Units 2 Story
Parcel size
19.65 acres
Building area
424,303 sq ft (assessor record)
Sewer
No connection on file (sewer or septic status not confirmed by the record — verify on site)
Flood zone
X — minimal flood hazard (FEMA)
Historic preservation
Not on file (City of Tucson HP layers)
Service on record
A 2024 permit was issued; completion is not confirmed in the available record; the permit description states “(1) Main Breaker And Meter Assembly Bussing Burning Up on 400 amp 6 meter pack 1ph 120/240 Replace Meter Assembly And 2/100 amp Main breaker for apartment 1290 - Like-for-like replacement.”.

See the property

County aerial photograph centered on 1901 N Wilmot Rd, parcel outlined

Pima County orthophoto (Pictometry 2024 / PAG 2023 / NAIP 2023 mosaic) — parcel outlined in yellow. Aerials can predate recent work and show nothing about what is inside; context, not evidence.

Is it time to upgrade?

  • Electrical service & distributionPermitted — completion not confirmedA 2024 permit specifies this work (the permit description states “(1) Main Breaker And Meter Assembly Bussing Burning Up on 400 amp 6 meter pack 1ph 120/240 Replace Meter Assembly And 2/100 amp Main breaker for apartment 1290 - Like-for-like replacement.”), but the available record does not show a final inspection. The work was permitted, but final completion is not confirmed. Official status: Inspections. City inspection record: COT - LCEL - Electrical Final approved 2024-10-11. TC-COM-1024-01964 — (1) Main Breaker And Meter Assembly Bussing Burning Up on 400 amp 6 meter pack 1ph 120/240 Replace Meter Assembly And 2/100 amp Main breaker for apartment 1290 - Like-for-like replacement.
  • Heating, cooling & mechanicalNot in this windowNothing in the permit records we read for this parcel that names this system. Worth knowing: a 2024 commercial building permit is on file (and 2 more like it) — work like this is often folded into a larger permit without being named, so open that record and check its scope before concluding anything. Packaged rooftop units work harder in Tucson than almost anywhere, so 12 to 15 years is a realistic service life rather than the 15 to 20 the industry quotes. Worth confirming from the equipment nameplate rather than the record. Replacing a rooftop unit is also an electrical question: the new unit's minimum circuit ampacity and its disconnect often differ from the old one.
  • Fire alarm & life safetyNot in this windowNothing in the permit records we read for this parcel that names this system. Any alarm or sprinkler work here predates this feed. For an occupied commercial building that is worth confirming from the panel and the inspection tags rather than assuming.
  • RoofNot in this windowNothing in the permit records we read for this parcel that names this system. Roof age matters electrically too: it sets what can be penetrated for new rooftop units, conduit, or solar.

A found permit means a lot. A missing one means less. We read the City of Tucson’s own permit file, not a recent extract of it — back to about 2006, and into the 1990s on properties with that much history. Microfiche before then was never fully digitised. Every record links to the city’s official file. A blank line does not say nothing was done: work gets done without permits all the time. The only way to know what is actually installed is to look at it.

What that usually means electrically

  • Era-based check — high priority

    Distribution gear this age is frequently past the point where the manufacturer still supports it. Breakers and fusible switches for obsolete lines can carry long lead times, which turns an outage into a shutdown. The permit record does not confirm this; an on-site inspection is required.

  • Worth looking at

    There are 6 open code enforcement cases on this parcel. An open case can hold up a permit, and if it touches unpermitted work the electrical scope usually has to be brought up to code as part of resolving it.

  • Worth confirming

    Multifamily property. House panels, unit meters, and common-area loads are usually metered and maintained separately — worth confirming which side of the meter a problem falls on before scheduling work.

  • Era-based check

    NFPA 70E expects arc-flash studies to be reviewed at least every five years, or after any change to the service. Buildings this age often have labeling that no longer matches the installed gear. The permit record does not confirm this; an on-site inspection is required.

  • Worth confirming

    There is an electrical reconnect permit from 2025. The service was disconnected at some point and brought back — usually after a vacancy, a utility disconnect, or work that required the power off. Worth knowing what prompted it.

Recorded sales (2)

Recorded transfers from the Pima County Assessor — 2 of 2
DatePriceType
1999-05-19$4,150,000Special Warranty Deed
1998-12-24$13,400,000Special Warranty Deed

Recorded sales are the sales the Pima County Assessor has on file from affidavits of property value — not every transfer, not listings, and not a valuation. Parties are never shown here. A sale with no permitted electrical work since is worth knowing before the next sale or a remodel.

Most recent permit on record for this parcel: 2025-03-26 (TR-ROW-0325-00391) — We need a bike lane closure to pave up to Wilmot Rd..

Permit history (35)

Permit history for this parcel — 8 of 35 records
DateRecordWhatStatusValue
2025-03-26finaledTR-ROW-0325-00391City permit recordRight-of-Way (ROW)We need a bike lane closure to pave up to Wilmot Rd.Complete
2025-02-13finaledSP-NRP-0225-00073City permit recordElectrical reconnect*Complete - Added to Utility Clearance Report* - - Electrical Reconnect Only - -Complete
2024-10-11expired 2025-04-09TC-COM-1024-01964City permit recordCommercial Building(1) Main Breaker And Meter Assembly Bussing Burning Up on 400 amp 6 meter pack 1ph 120/240 Replace Meter Assembly And 2/100 amp Main breaker for apartment 1290 - Like-for-like replacement.Inspections
2024-09-20finaledTC-COM-0924-01838City permit recordCommercial BuildingFire Restoration of Apartment. Unit 2094Inspections complete
2024-09-20finaledTC-COM-0924-01839City permit recordCommercial BuildingFire Restoration of Apartment. Unit 2095Inspections complete
2024-09-20finaledTC-COM-0924-01840City permit recordCommercial BuildingFire Restoration of Apartment. Unit 2096Inspections complete
2024-09-20finaledTC-COM-0924-01841City permit recordCommercial BuildingWater Restoration of Apartment. Unit 1094Inspections complete
2024-09-20finaledTC-COM-0924-01842City permit recordCommercial BuildingFire Restoration of Apartment. Unit 1095Inspections complete
Show 27 older records
Permit history for this parcel — remaining 27 records
DateRecordWhatStatusValue
2024-09-20finaledTC-RES-0924-05466City permit recordResidential Building - One or Two FamilyElectric has been off since January. Looking to restore electric.Complete
2024-07-31finaledTC-COM-0724-01473City permit recordFence / wallCE-VIO0624-02113 Emergency Repair stick framed wall 8lf x 9'h. R-13 128 SQ FT. 1/2 DRYWALL 128 SQ FT. STUCCO 128 SQ FT. NO FOUNDATION/ NO PLUMBING OR ELECTRICAL.Inspections complete
2023-11-13expired 2024-07-07TC-COM-1123-02643City permit recordCommercial BuildingWork is for Replacement of damaged disconnects and Panel. Like For Like Replacement This Service is labeled '1701 N Wilmot OWN1' and shows as such in TEP system. Per Pima County Addressing they can not add this to their system since it is an owners panel for this apartment complex even though it is attached to the main office. ** Per TEP they Will not reconnect after the repairs are done if they don't Get Clearance issued that shows the '1701 N Wilmot OWN1' designation. They will have to have the permit issued with the address and designation. Please give me a call on my cell 520-270-8500 if you have any questionsIssued
2023-05-23expired 2024-01-21TC-COM-0523-01355City permit recordCommercial BuildingChange Out Meter Bussing, Use Existing bussing from Meter socket not in useIssued
2023-04-26expired 2023-12-06TC-RES-0423-04748City permit recordResidential Building - One or Two FamilyResident was evicted Month and a half ago. light was never put back into property name. Tep say light has been off since 01/2022Issued
2023-03-27expired 2023-09-23TC-RES-0323-03891City permit recordResidential Building - One or Two FamilyVOIDED DUPLICATE PERMIT USE PERMIT TC-RES-0123-02271 Residence has no power and is occupied.Void
2023-02-02expired 2023-12-05TC-COM-0223-00578City permit recordCommercial BuildingLike for like, meter locked, need permit for power reconnect 125amp panelExpired
2023-01-20expired 2023-12-05TC-RES-0123-02271City permit recordResidential Building - One or Two FamilyELECTRIC RECONNECT Need electric service put back to management. resident no longer lives here.Issued
2022-02-08finaledT22CM00962City permit recordCOMBOReplace Meter Busing Like for LikeFinal
2021-08-17finaledT21CM06652City permit recordCOMBOReplace meter busingFinal
2021-06-25finaledT21CM05281City permit recordCOMBOREPLACE BUSSING IN METER PACK IMMEDIATELY BELOW METER SOCKET WHERE MAIN BREAKER CLIPS-ONFinal
2019-12-16expired 2020-06-17T19BU00622City permit recordPool / spaDEMO POOLClosed
2017-10-26finaledT17RW04795City permit recordROWASPHALT PATCH REPAIR FOR SWGFinal
2017-10-02finaledT17CM07466City permit recordCOMBOREPL 4 METER PACKFinal
2017-08-08finaledT17RW03434City permit recordROWREMOVE 30' OF EXISTING SIDEWALK. INSTALL NEW 30' X 8' X 6" DEEP CONCRETE PAD. INSTALL NEW TUCSON -STYLE SHELTER. 8'4" OF ROW. PAD # 30 TC # 1Final
2017-01-24finaledT17RW00391City permit recordROWEMERGENCY (2) 5 X 5 IN DIRT AND (2) IN BLKTOP -TO REPAIR GAS LINE WORK ORDER # 88700000Final
2015-08-04finaledT15CM05353City permit recordCOMBOT15DV04731-CAR DAMAGE REPAIRL of c
2015-05-07finaledT15EL00080City permit recordELECTElectric Reconnect (VH)Final
2015-04-08finaledT15OT00479City permit recordSIGN90 DAY BANNER 4-9-15 TO 7-8-15Final
2015-03-13finaledT15OT00344City permit recordSIGN(22756) 1-NON ILLUM DFFinal
2015-02-17finaledT15CM01014City permit recordCOMBOFIRE RESORATION;RESL of c
2014-11-18finaledT14CM07856City permit recordCOMBOAPARTMENT CAR DAMAGE REPAIRS-LIKE FOR LIKEL of c
2011-09-14finaledT11EL02443City permit recordELECTreplace main breakerFinal
2011-08-31finaledT11EL02332City permit recordELECTRECONNECT:ELECTRIC APTFinal
2011-03-11finaledT11EL00713City permit recordELECTREPLACE MAIN ELEC. BREAKERFinal
2009-05-19finaledT09OT00995City permit recordSIGN16676Final
2009-05-19finaledT09OT00996City permit recordSIGN16675Final

How to read the status column: Final / Complete / C of O — city records show the permit was finalized. Issued — the work was permitted, but final completion is not confirmed. Applied / In review / Approved / Fees paid — proposed, not completion. Expired — the permit expired without a confirmed final status. Void / Withdrawn / Canceled — not evidence the work was installed. Any other status is shown exactly as the issuing office records it, without a completion reading.

Code enforcement (71)

Code cases and housing-code violations recorded against this parcel, by category. Closed cases stay on the record, and most of these are closed — check the status column. We show the category and the official record number rather than the complaint text, which often names people who have nothing to do with the property.

Code enforcement history for this parcel — 8 of 71 records
DateRecordWhatStatus
2026-08-13CE-VIO0826-03358Code enforcement caseCode enforcement caseReceived
2025-08-21CE-VIO0825-03562Code enforcement caseCode enforcement caseClosed - unfounded
2025-06-18CE-VIO0625-02648Code enforcement caseCode enforcement caseClosed - resolved
2025-02-28CE-VIO0225-00895Code enforcement caseCode enforcement caseClosed - unfounded
2024-11-08CE-VIO1124-04457Code enforcement caseCode enforcement caseClosed - unfounded
2024-09-20CE-VIO0924-03816Code enforcement caseCode enforcement caseClosed - unfounded
2024-08-23CE-VIO0824-03418Code enforcement caseCode enforcement caseActive
2024-08-20CE-VIO0824-03324Code enforcement caseCode enforcement caseClosed - unfounded

63 older records are not shown here. — each links to its official file.

Record numbers link to the City of Tucson’s official file. Highlighted rows are the ones that imply electrical work or an unpermitted-work finding.

This is an inference from public records — the year a structure was built, how it is classified, and what has been permitted. It is not an inspection, and nothing here confirms what is actually installed at this address. The only way to know is to look in the panel. See an error in this public-record report? Report a correction · About this data.

Planning work at this property?

Arizona Electrical Solutions provides electrical, HVAC, underground, design-build, tenant-improvement and general-contracting services in Tucson (four Arizona ROC licenses). Choose what describes you and send us this property’s address and public-record report for review — the address, parcel, report link and permit record travel with the request automatically.

What describes you?
Call (520) 308-6235

The contractor’s read is a plain-English brief of the record above, written by AI — what it shows across electrical, mechanical and the building itself, what is missing for the era, and what to verify on site.

How this report was built

This is a reading of public records for parcel 12101012F — 35 permits on file from 2009 to 2025 (9 commercial building, 7 combo, 4 residential building - one or two family, 4 elect) and 71 code enforcement cases — assembled from the Pima County parcel file, the City of Tucson’s Property Research Online file (permits back to about 2006, further on some parcels), and the City’s GIS permit and code-enforcement layers (2022 onward). Public records last checked 2026-08-17; the record is re-read at least weekly. Each permit and code case links to its official file. The verdicts are inferences from what was permitted and when, and from the era the building went up; they are not an inspection, and nothing here confirms what is installed. A permit that is present is strong evidence; a permit that is absent is weak evidence — plenty of work is never permitted, and older county records were only partly moved online.

The interactive version of this report can also read the plan sheets behind a City of Tucson permit and write a contractor’s brief of the whole record — those buttons appear once the page finishes loading. Written and maintained by Arizona Electrical Solutions, LLC, a licensed Tucson contractor (ROC 276948 CR-11 electrical, ROC 326401 CR-39 HVAC, ROC 329360 KB-1, ROC 312437 KA).

Look up a different address: Tucson permit history & electrical upgrade check · see permit data by neighborhood.