Field Guide • Testing & Workmanship
How to Megger Test a Motor or Feeder
Updated July 16, 2026 • Written by the field team at Arizona Electrical Solutions. All field guides →
A megohmmeter — everybody calls it a megger — puts a DC test voltage across insulation and measures the leakage current through it, displayed as megohms. It answers one question before you energize anything: is this insulation intact, or is there a path to ground or between phases waiting to trip a breaker or cook a winding?
On commercial work you'll megger in three situations. Before energization — NEC 110.7 requires completed wiring free from short circuits and ground faults, and the megger is how you prove it. Troubleshooting — a motor tripping overloads, a feeder breaker that won't hold. And maintenance baselines — annual readings on critical motors let you watch insulation trend down and swap the motor on your schedule instead of production's. The test itself takes minutes; the real work is isolation and interpretation.
Safety first. This is work for qualified persons under a licensed contractor — a megger puts 1,000 volts DC or more on conductors. De-energize, apply lockout/tagout, and verify absence of voltage on every conductor before touching anything, with PPE appropriate to the task per NFPA 70E. Keep everyone clear of both ends of the circuit while test voltage is applied — the far end of a feeder is as live as the test lead. Permits and inspections run through the local AHJ, and the locally adopted NEC edition governs; this guide uses 2023 numbering.
What you'll need
- Megohmmeter with 500V and 1,000V DC ranges, calibration up to date
- Voltage tester rated for the system, verified live-dead-live
- Lockout/tagout locks, tags, and hasps
- PPE per the task and NFPA 70E arc flash assessment
- Insulated hand tools for lifting and landing conductors
- Grounding jumper for bleeding off test charge
- Wire markers or phase tape to re-land conductors correctly
- Test record form — equipment ID, readings, temperature, date, test voltage
- Thermometer or IR gun for winding/ambient temperature
Code references
| NEC 110.7 | Completed wiring installations must be free from short circuits and ground faults — the megger test is the proof. |
| NEC 110.14(D) | Terminations must be torqued per equipment marking when you re-land conductors after testing. |
| NEC 250.4(A)(5) | Requires an effective ground-fault current path — why phase-to-ground insulation integrity matters. |
| NEC 90.4 | The AHJ interprets and enforces the locally adopted Code edition. |
| NFPA 70E Art. 120 | Establishing an electrically safe work condition: LOTO and verifying absence of voltage before testing. |
| IEEE 43 | Recommended practice for motor winding insulation resistance: test voltages, 40°C correction, minimum values. |
Section numbers follow the 2023 NEC; the edition adopted by your jurisdiction governs.
Step by Step
How to Megger Test a Motor or Feeder
1. Pick the right test voltage
Test voltage follows the rated voltage of what you're testing. Standard practice per NETA ATS Table 100.1: 250V and below gets 500V DC; 251V through 600V — 480V motors and feeders, the bulk of commercial work — gets 1,000V DC. Medium-voltage gear steps up to 2,500V or 5,000V DC, but that's specialty testing.
For motor windings, IEEE 43 accepts 500V DC on machines rated under 1,000V, so either 500V or 1,000V is defensible on a 480V motor — just use the same voltage every time on the same machine so your trend data means something. Never test above the insulation rating: a 120V control circuit doesn't get 1,000 volts.
2. De-energize, lock out, verify dead
Open the disconnecting means, apply your lock and tag, and verify absence of voltage phase-to-phase and phase-to-ground on every conductor you're about to touch, using a meter proven on a known live source before and after. That's the electrically safe work condition of NFPA 70E Article 120 — non-negotiable when you're about to handle bare conductor ends.
On a feeder, control both ends. If the far end lands in a panel someone else can access, lock it out or station somebody there — test voltage appears at every point on the conductor.
3. Isolate the circuit — get the electronics off
A megger will destroy solid-state equipment. Before testing, disconnect anything electronic on the conductors under test: VFDs, soft starters, surge protective devices, power monitors, control transformers, pilot lights, capacitors. On a drive-fed motor, lift the motor leads at the drive's output terminals — never megger through a VFD in either direction.
For a feeder, isolate at both ends and lift load-side connections so you're testing conductors only — anything left connected either drags the reading down or gets damaged. For a motor, disconnect at the peckerhead or the starter's load terminals, and note whether the motor leads are in the reading so the next test matches.
4. Test a feeder: phase-to-phase and phase-to-ground
With conductors isolated at both ends, test every combination. Three-phase feeder with neutral: A-B, B-C, C-A, then A-G, B-G, C-G, and N-G with the neutral lifted from the bar (a bonded neutral reads zero to ground by design). Apply the voltage for one minute and record at the one-minute mark — resistance climbs as the DC charge stabilizes, and consistent timing is what makes readings comparable.
Healthy new conductors in dry conduit read hundreds of megohms to gigohms. Single-digit megohms on a new pull means damage — insulation skinned at a coupling, a nick at a bushing, or water in the raceway. One low phase points at physical damage; all three uniformly low points at moisture or contamination.
5. Test a motor: windings to ground
On a standard three-phase motor the windings are internally connected (wye or delta), so phase-to-phase readings just measure copper continuity — the meaningful test is winding-to-ground. Connect one lead to a motor lead and the other to the frame at a clean, paint-free spot, and test for one minute. Because the windings are tied together, one reading tests all of them; on a 9- or 12-lead machine with the jumpers pulled, test each winding group to ground and to the other groups.
While you're in the peckerhead, look. Darkened insulation, a varnish smell, brittle leads, or moisture all corroborate a low reading. A marginal motor that sat in a wet room may be moisture-soaked and recoverable with a bake-out; burned insulation is done.
6. Interpret the numbers — and correct for temperature
The old rule of thumb is 1 megohm plus 1 megohm per kV of rated voltage — roughly a 1.5 megohm floor for a 480V system. Treat that as a do-not-energize line, not a passing grade. IEEE 43 sets 5 megohms (corrected to 40°C) as the minimum for typical random-wound motors under 1,000V, and NETA ATS Table 100.1 calls for 100 megohms on 600V-class cable and equipment. A new installation barely above the rule-of-thumb floor has a problem even though it technically passed.
Temperature matters: insulation resistance roughly halves for every 10°C rise, so a motor pulled off line hot reads a fraction of what it reads cold the next morning. Record the temperature with every reading and correct to the 40°C base per IEEE 43 before comparing against minimums or last year's baseline — otherwise your trend line is measuring the weather.
7. Discharge, record, restore
The DC test charges the circuit like a capacitor, and long feeders and big windings store real energy. After each reading, discharge through the megger's discharge function or a grounding jumper, leave the ground applied at least four times as long as the test voltage was, and verify zero volts before touching conductors.
Record everything on the spot: equipment ID, date, test voltage, each reading, temperature, and what was connected. A single reading tells you pass or fail today; a series on the same motor tells you it's lost half its insulation resistance in two years and belongs on the replacement budget. Then re-land conductors per your markings, torque terminations per the equipment labeling (NEC 110.14(D)), reconnect the electronics, and clear LOTO per procedure.
Watch Out
Common mistakes
- Meggering through a VFD or with surge protective devices still connected — the DC test voltage destroys solid-state components.
- Testing at 1,000V on circuits rated below the test voltage, which can fail insulation that was healthy at its rated voltage.
- Leaving loads or control devices connected on a feeder test, so the meter reads through the load and reports a meaningless low number.
- Ignoring temperature — comparing a hot-motor reading against a cold baseline makes good insulation look like it's failing, or hides a real decline.
- Skipping the discharge step and leaving a charged feeder that bites the next person who touches it.
- Meggering a bonded neutral to ground without lifting it first and condemning a good conductor for reading zero.
- Writing nothing down — without a recorded baseline at a known test voltage and temperature, next year's reading is uninterpretable.
FAQ
Frequently asked questions
What is a good megger reading for a 480V motor?
IEEE 43 sets a minimum of 5 megohms corrected to 40°C for typical random-wound motors under 1,000 volts, and a healthy motor usually reads far higher. Anything near the old 1-megohm-per-kV rule of thumb is a do-not-energize condition, not a pass.
What test voltage should I use on a 480V system?
1,000V DC is standard for conductors and equipment rated 251 to 600 volts per NETA ATS Table 100.1, and IEEE 43 also accepts 500V DC for motor windings under 1,000 volts. Use the same test voltage every time on the same equipment so readings stay comparable.
Will a megger damage a VFD or other electronics?
Yes. The DC test voltage destroys drive output transistors, surge protective devices, and other solid-state components. Disconnect all electronics before testing, and never megger through a VFD in either direction.
Does the NEC require megger testing?
The NEC does not mandate a specific test, but NEC 110.7 requires completed wiring to be free from short circuits and ground faults, and the megger test is the accepted way to demonstrate that. Many project specifications require documented readings before energization.
How does temperature affect insulation resistance readings?
Insulation resistance roughly halves for every 10°C increase, so a hot winding reads dramatically lower than the same winding cold. Record the temperature with every reading and correct to the 40°C base per IEEE 43 before comparing readings.
Why do I have to discharge the circuit after a megger test?
The DC test voltage charges conductors and windings like a capacitor, and that stored energy can deliver a serious shock. Ground the circuit for at least four times the test duration and verify zero volts before touching conductors.
Keep Going
Related guides & tools
Do this work every day?
We're hiring electricians and HVAC techs on commercial projects across Arizona — see open positions. Need this done on your project instead? We self-perform it.
Request a Bid